Product Overview
- R-410A refrigerant used in all models
- Compact (about 2 sq. ft. of floor space)
- Unique free-floating chassis
- 10” crimped and beaded duct-collar ready to attach flex-duct
- Drain plan included
- Easy to connect right, left or rear drain connection
- Corrosion resistant interior
- Easy to install front, left or right hand into closet on an outside wall (Does not require an HVAC technician)
- Remote thermostat ready; 24V transformer
- Standard safety power disconnect
- All units are shipped (on pallet) with return air filter installed
- Electronic control panel on unit for easy diagnostics and servicing
- Architectural louvers required and available in standard extruded aluminum (AVAGK01SB)
- Exterior Wall Adaptors (AVEWA05-08A or ACEWA08-14A), Digital/Manual thermostat (PHWT-A150H) and Digital/Programmable (PHWT-A200) and return air grilles and (AVLWP01A-R or L) are available separately
- No refrigerant lines running from floor to floor
12,000 BTU VTAC Models Available: | AVH123H25AXXX | AVH123H35AXXX | AVH123H50AXXX |
---|---|---|---|
ELECTRIC HEAT DATA: | |||
Volts: | 208 / 230 | 208 / 230 | 208 / 230 |
Electric Heater Size (Kw): | 2.1 / 2.5 | 2.8 / 3.4 | 4.1 / 5.0 |
Watts: | 2050 / 2500 | 2780 / 3400 | 4090 / 5000 |
BTUs: | 7000 / 8500 | 9500 / 11600 | 13900 / 17000 |
Heating Amps: | 11.1 / 12.0 | 14.6 / 16.0 | 20.9 / 22.9 |
Minimum Circuit Ampacity: | 15 | 19.9 | 28.6 |
Branch Circuit Fuse (Amps): | 15 | 20 | 30 |
Basic Heater Size: | 2.5 Kw | 3.4 Kw | 5.0 Kw |
Tech Specs
WARNING!