Shop by Brand > S and P Commercial Exhaust Fans > S & P STXB12RHULMH1S Upblast Belt Drive Centrifugal Restaurant Exhauster - 12" Wheel, 115 Volt

S & P STXB12RHULMH1S Upblast Belt Drive Centrifugal Restaurant Exhauster - 12" Wheel, 115 Volt

SolerPalau SolerPalau
Availability: Usually Leaves Warehouse in 2 - 3 Business Days
Product Code:SOLERPALAU-STXB12RHULMH1S
Price: $889.00
Qty
or
Loading Bread...
Free Shipping on all Orders!
  • Description

    The STXB-UL762 models are upblast belt driven centrifugal exhausters. They are listed for both general applications and suitable for restaurant applications*. The STXB12RHULMH1S is a size 12 model, with a fan wheel of 12 inches in diameter. It features heavy duty construction and is rated for continuous use. The fan wheel is constructed for maximum efficiency featuring aluminum construction and a backward-inclined curved centrifugal wheel. It is dynamically balanced for long lasting, smooth operation. Model STXB exhausters are best suited of removal of dirty, contaminated and/or high temperature air. Uses for the STXB exhausters include restaurant hood and similar kitchen exhaust ventilation, fume and smoke removal as well as laboratory fume hood exhaust and chemical process exhaust. For grease removal applications, fan must be installed per NFPA 96 with a 40" discharge height and hinged access base

    The STXB12RHULMH1S can be used in a ducted or non-ducted installation, either vertically through the roof or horizontally through a sidewall. These installation possibilities allow for shorter duct runs and therefore the exhauster can be installed near the area to be ventilated. The STXB12RHULMH1S will produce 1602 CFMs at zero static pressure.

    The motor is a single speed open drip-proof motor. The cover is easily removed for maintenance. The housing includes stainless steel exterior fasteners and a disconnect.

    An automatic belt tensioner is available. The addition of this helps to eliminate the risk of over-tensioning the drive components. The 100070 Automatic Belt Tensioner must be ordered at the time of your roof exhauster and it is factory-installed.

    S&P STXB model Upblast Belt Drive Centrifugal Exhausters with roof installation can be used to replace Greenheck CUBE, Loren Cook ACRUB/VCR, Pennbarry FX/WFX, Carnes VUBK, Acme PNURF/PNURG and Fantech 5BDU models.

    S&P STXB model Upblast Belt Drive Centrifugal Exhausters with sidewall installation can be used to replace Greenheck CWB, Loren Cook ACWB, Pennbarry WFX, Carnes VWBK and, Acme PWB models.

    *Neither a damper nor a birdscreen can be used in restaurant/grease applications. Restaurant curbs must be 18" high per NFPA-96 which prohibits the use of backdraft damper for grease removal..
  • Tech Specs

    Net Weight (lbs.)
    136
    Wheel Size (In.)
    12 "
    Horsepower (HP)
    1/4
    Max. BHP
    0.26
    RPMs
    1450
    Max. Static Pressure WG (In.)
    3/4 "
    Sones Level
    11.8 @ 1/4 SP
    CFM @ Zero Static Pressure
    1602
    Installation
    Both Roof and Sidewall
    Type of Drive
    Belt Drive
    Roof Opening (In.)
    15.5 "
    Voltage
    110-120V
    Certifications
    AMCA Air and Sound Licensed, UL 762 Listed
    Warranty Detail
    2 Year Limited Warranty, 1 Year Motor Warranty
  • Manuals and Guides

  • More Info